Market / Safety & sensing
AmaYon

Transformer - VAN

A dedicated van for efficient transformer testing and diagnostics.

Updated 2026-11-0228 features
Transformer - VAN

Basic Configuration

Short circuit impedance

Measures the impedance during short circuit conditions.

SpecificationValue
Availabilitystandard
  • Enhances testing accuracy

Power losses for no-load and short circuit conditions

Assesses power losses under different conditions.

SpecificationValue
Availabilitystandard
  • Improves efficiency analysis

Frequency response analysis

Analyzes the frequency response of transformers.

SpecificationValue
Availabilitystandard
  • Facilitates condition assessment
Frequency response analysis

Moisture-in-cellulose assessment with DFR technique

Evaluates moisture levels in transformer insulation.

SpecificationValue
Availabilitystandard
  • Critical for insulation health

Optional Features

Central computer with touch screen

Provides an intuitive interface for test management.

SpecificationValue
Availabilityoption
  • Enhances user experience

Control unit

Manages the testing processes and data collection.

SpecificationValue
Availabilityoption
  • Streamlines operations

DC winding resistance / onload tap changer continuity test

Tests winding resistance and continuity of tap changers.

SpecificationValue
Availabilityoption
  • Ensures reliable transformer operation

Turns ratio and vector group verification

Verifies turns ratio and vector group of transformers.

SpecificationValue
Availabilityoption
  • Confirms transformer configuration

Insulation resistance

Measures the insulation resistance of transformer windings.

SpecificationValue
Availabilityoption
  • Critical for safety and performance

Capacitance and power factor/ dissipation factor (and exciti

Assesses capacitance and power factor for transformers and bushings.

SpecificationValue
Availabilityoption
  • Important for diagnostic evaluation

Withstand tests at elevated voltage up to 100 kV AC 50 Hz an

Conducts high voltage withstand tests.

SpecificationValue
Availabilityoption
  • Ensures transformer reliability under stress

Oil dielectric strength measurements

Measures the dielectric strength of transformer oil.

SpecificationValue
Availabilityoption
  • Essential for insulation assessment

Test Leads

HV Test Leads

High voltage test leads for insulation assessment.

SpecificationValue
Length30 m
  • Facilitates accurate insulation testing.

LV Test Leads

Low voltage test leads for winding resistance and turns ratio.

SpecificationValue
Length30 m
  • Essential for comprehensive transformer testing.
LV Test Leads

Safety Equipment

External Safety Box

Provides additional safety for testing operations.

  • Enhances user safety during tests.
External Safety Box

Safety Monitoring System

Monitors all safety-relevant parameters.

  • Ensures safe operation of the test van.

Safety Equipment Compliance

Safety equipment in accordance with BGI 891 and VDE 0104.

  • Meets industry safety standards.
Safety Equipment Compliance

Power Supply

Power Supply Options

Supports various power supply configurations.

SpecificationValue
Voltage100-240 V
Frequency50-60 Hz
  • Versatile for different operational environments.

Built-in Power Generator

Optional generator for independent power supply.

SpecificationValue
Power5 kVA and higher
  • Ensures continuous operation in remote locations.

Testing Capabilities

Insulation Testing

Conducts various insulation tests.

SpecificationValue
Test Voltage, DCup to 5, 10 or 15 kV
Measurement Range100 kOhm…15 TOhm
Charging Current2 mA, 6 mA (short circuit)
Noise Immunity8 mA
  • Provides reliable insulation assessment.

Capacitance and Dissipation Factor Testing

Measures capacitance and dissipation factor.

SpecificationValue
Test Voltage, AC0-12 kV
Test Current (at 12 kV)300 mA (4 minutes), 100 mA (continuous)
Test Frequency Range45-70 Hz (12 kV), 15-400 Hz (4 kV), 1-500 Hz (25
  • Accurate measurement of dielectric properties.

Winding Resistance Testing

Tests winding resistance and OLTC.

SpecificationValue
Test Currentup to 10 A (optional up to 50 A)
Measurement Range1 μOhm – 2 kOhm
Accuracy+/- 0.25%
  • Ensures precise winding resistance evaluation.

Turns Ratio and Vector Group Testing

Measures turns ratio and phase deviation.

SpecificationValue
Excitation Voltageup to 80 V
Ratio Measurement Range0.8 – 45000
Phase Deviation+/-90°
Accuracy+/-0.1%... +/- 0.3%
  • Critical for transformer performance analysis.

Voltage Withstand Testing

Tests voltage withstand capabilities.

SpecificationValue
AC Test Voltage0…100 kV
DC Test Voltage0…70 kV
Load Capacitance0.01-1.9 nF
Leakage Current Measurementup to 100 mA
Max Power Consumption20 kVA
  • Validates insulation integrity under high voltage.

Control and Data Acquisition

Control Software

Utilizes PowerDB for data management.

  • Streamlines reporting and data comparison.
Control Software

Operating System

Runs on a basic operating system.

SpecificationValue
OSWIN 7
  • Familiar interface for users.
Operating System

Interface Options

Multiple interface options for connectivity.

SpecificationValue
—RS 232, USB, Ethernet
  • Flexible connectivity for various devices.

Uninterruptable Power Supply

Provides backup power for the industrial PC.

SpecificationValue
Duration7 min
  • Ensures data integrity during power loss.
Ask AmaYon a question about Transformer - VAN